Skoči na glavni sadržaj

Izvorni znanstveni članak

https://doi.org/10.13044/j.sdewes.d5.0130

The use of Dynamic Mathematical Models for improving the Designs of upgraded Wastewater Treatment Plants

Nadja Hvala ; Department of Systems and Control, Jožef Stefan Institute, Jamova cesta 39, SI-1000 Ljubljana, Slovenia
Darko Vrečko ; Department of Systems and Control, Jožef Stefan Institute, Jamova cesta 39, SI-1000 Ljubljana, Slovenia
Meta Levstek ; JP CČN Domžale-Kamnik d.o.o., Študljanska 91, SI-1230, Domžale, Slovenia
Cirila Bordon ; JP Vodovod-Kanalizacija d.o.o., Vodovodna cesta 90, SI-1000 Ljubljana, Slovenia


Puni tekst: engleski pdf 1.402 Kb

str. 15-31

preuzimanja: 827

citiraj


Sažetak

Mathematical models and simulation are becoming increasingly used tools in the optimization of wastewater treatment plants. In this paper, the use of these tools is presented for wastewater treatment plant upgrading. Two case studies are presented, which will be upgraded for tertiary treatment to achieve effluent total nitrogen and total phosphorous concentrations below 10 mg/l and 1 mg/l, respectively. The plant performance after upgrading was assessed by first designing the process model, before upgrading the model for future operation under dynamic influent conditions. Long-term
simulations revealed some bottlenecks in the upgraded plant performance and thus helped to improve the plant designs. In one case the total volume of the reactors was increased subsequently, while in the other case tighter denitrification control or additional reject water treatment was proposed. These results indicate that mathematical models can be considered as valuable tools to complement the established wastewater treatment plant design procedures. Advantages are gained by simulating the operation
under dynamic operating conditions, precise wastewater characterization, as well as adjustment of stoichiometric and kinetic parameters to a particular wastewater treatment plant operation.

Ključne riječi

Biological wastewater treatment; Mathematical model; Simulation; GPS-X; Plant upgrading; Activated sludge process; Sequencing batch reactor; Tertiary treatment

Hrčak ID:

170089

URI

https://hrcak.srce.hr/170089

Datum izdavanja:

31.3.2017.

Posjeta: 1.620 *