Skoči na glavni sadržaj

Prethodno priopćenje

DYNAMIC ANALYSIS OF WIND FARM OPERATION INTEGRATED IN POWER SYSTEM BASED ON SYNCHRONIZED MEASUREMENTS

Srđan SKOK ; Tehnički fakultet Sveučilišta u Rijeci
Vedran KIRINČIĆ ; Tehnički fakultet Sveučilišta u Rijeci
Kristijan FRLAN ; HEP – Operator prijenosnog sustava d.o.o.


Puni tekst: hrvatski pdf 909 Kb

str. 73-83

preuzimanja: 1.297

citiraj

Puni tekst: engleski pdf 909 Kb

str. 73-83

preuzimanja: 1.436

citiraj


Sažetak

Reliable and safe control of the power system is based on knowing current and voltage conditions during normal and irregular states. Real time dynamic disturbance responses, caused by characteristic events, are especially important. Wind farm Vrataruša is currently the only wind farm connected to the Croatian transmission system. This paper focuses on the impact of the wind farm Vrataruša on the system in the transmission area Rijeka. Static calculations (power flow calculation and short circuit current calculation) and dynamic analyses (transient phenomena) comprise normal, irregular and outage operational states, as well as their impact on a protection system and on overall power system stability. Analyses are based on a mathematical model of the transmission system area Rijeka, verified by synchronized voltage and current phasor measurements.

Ključne riječi

synchronized measurements; dynamic modeling; wind farm; differential protection; phasor; PMU

Hrčak ID:

56096

URI

https://hrcak.srce.hr/56096

Datum izdavanja:

23.7.2010.

Podaci na drugim jezicima: hrvatski

Posjeta: 3.868 *