Skoči na glavni sadržaj

Izvorni znanstveni članak

LIGHTNING DATA UTILIZATION IN POWER SYSTEM CONTROL

BOJAN FRANC ; University of Zagreb Faculty of Electrical Engineering and Computing
IVO UGLEŠIĆ ; University of Zagreb Faculty of Electrical Engineering and Computing
SILVIA PILIŠKIĆ ; Croatian Transmission System Operator Ltd.


Puni tekst: engleski pdf 1.761 Kb

preuzimanja: 342

citiraj


Sažetak

Lightning location systems (LLS) provide data on lightning activity such as
lightning type, GPS location, exact time of the lightning stroke, lightning current
amplitude, measurement error, etc. The proper application of LLS data using
customized software support can be a powerful decision-making tool in the control,
maintenance and development of power systems. The utilization of lightning data in
power systems requires a customized software support with specific functionalities.
Software functionalities include real time lightning activity visualization with
alarm function; analysis, reports and historical lightning activity visualization;
spatial correlation between lightning data and alarm zones around geographically
represented power system’s objects (power lines, power facilities, etc.); calculation of
lightning statistics; generation of wide area lightning density maps, generation of
high resolution lightning density maps inspecting alarm zones around the power
lines; real time correlation between lightning activity and the power system
protection equipment (distant protection relays), gathered through the SCADA
system. In this paper, emphasis will be given to the application in correlation
between faults and outages in the power network and lightning strokes. Today,
B. Franc, I. Uglešić, S. Piliškić, Lightning data utilization in power system control, Journal of Energy, vol. 64 (2015) Special Issue, p. 62-77
many power companies monitor data related to circuit breaker operation or reclosing
using various equipment. Such equipment allows online monitoring of
circuit breakers and alarm statuses of equipment in substations

Ključne riječi

panies monitor data related to circuit breaker operation or reclosing using various equipme

Hrčak ID:

199276

URI

https://hrcak.srce.hr/199276

Datum izdavanja:

15.9.2017.

Posjeta: 784 *