Sažetak

In the operation of the broadcasting transmitter, during a lightning storm,
comes to frequent surge arrester failures in the switchgear of the broadcasting
transmitter and along the 10 kV supply cable (surge arresters in the cable section
boxes). Analysis of lightning strokes to the broadcasting transmitter is given in the
paper. EMTP simulation of surge arresters loading was conducted. The energy
overload of surge arresters is due to lightning flash with more than one lightning
strokes or more lightning flashes in short time. Recommendations were also given
for improvement of existing surge protection and reduction the number of surge
arresters failures.

Ključne riječi

broadcasting transmitter; lightning stroke; overheating; surge arrester failure