During their lifespan all primary HV equipment installed in the power system is subjected to transients. Therefore, it is necessary to adequately dimension and protect the equipment. However, in the networks with high share of renewables, power electronics, cables or near gas insulated substation (GIS), the failure can occur even though good practices of insulation coordination are fulfilled. In this paper, a high-frequency power transformer model is presented. Such model is based on measurements of admittance matrix and is adequate for simulation of fast front transients in EMTP like software. Additionally, simulations of transferred lightning and switching overvoltages are given for the observed power transformer unit.

Ključne riječi

fast front transients; power transformer; EMTP; measurement; admittance matrix