Skip to the main content

Original scientific paper

DGA monitor accuracy – Data and decisions

Tony McGrail


Full text: english pdf 386 Kb

page 34-38

downloads: 67

cite


Abstract

This article explores the intricacies of DGA monitor accuracy, emphasising the challenges in extracting dissolved gases from transformer oil. Despite international standards like IEC 60567 recommending a maximum accuracy of 15% for complete DGA systems, real-world application, as reflected in CIGRE brochures, suggests a potential deviation closer to 50%. The implications of varying accuracies on diagnoses, particularly when employing diagnostic tools like the Duval triangle, are analysed.

Keywords

DGA; DGA monitor; accuracy; extraction method; CIGRE; diagnoses; Duval triangle

Hrčak ID:

308706

URI

https://hrcak.srce.hr/308706

Publication date:

10.10.2023.

Visits: 135 *