Impact of controllable superconducting series reactor in transient recovery voltage of circuit breaker

Amir Heidary
Hassan Moradi CheshmehBeigi
Ali Mehrizi-Sani


Full text: english pdf 1.747 Kb

page 54-69

downloads: 188

cite


Abstract

Series reactors as fault current limiters (FCLs) are extensively employed to enhance power grid protection issues. Utilizing superconducting technology is a viable solution to approach FCLs toward commercializing. The concern of transient recovery voltage (TRV) of the circuit breaker becomes more considerable due to FCL’s high stored energy in the case of fault current limiting mode. This paper firstly focuses on the analysis of TRV under the presence of an inductive-based superconducting fault current limiter (SFCL) installed in a power grid, and then it investigates the impact of a controllable
superconducting series reactor (CSSR) in TRV of the circuit breaker. The obtained results show that the synchronous operation of a CSSR with a circuit breaker substantially declines TRV.

Keywords

circuit breaker, fault current limiter, superconducting series reactor, transient recovery voltage

Hrčak ID:

263822

URI

https://hrcak.srce.hr/263822

Publication date:

20.8.2021.

Visits: 556 *