Skoči na glavni sadržaj

Izvorni znanstveni članak

Short-circuit withstand capability of power transformers - Part I

Rene Smeets orcid id orcid.org/0000-0001-5788-2858 ; Kema Laboratories, DNV GL


Puni tekst: engleski pdf 10.699 Kb

str. 78-83

preuzimanja: 1.566

citiraj


Sažetak

This article discusses verification of the ability of a transformer to survive short circuit. Fault current leads to large axial and radial forces on windings, which have to be managed by proper structural design. Test experience, showing a failure rate of 20-25 % of well-prepared transformers, suggests that the highest degree of reliability with respect to short-circuit withstand verification is ensured through full-scale testing in accordance with the international standards. The prime failure mode is winding deformation, but many other deficiencies, which would not be discovered in a design review, have also been observed. Since 2016, KEMA Laboratories is equipped to short-circuit test transformers up to the 800 kV class.

Ključne riječi

power transformer; short circuit; testing; certification; reliability

Hrčak ID:

179590

URI

https://hrcak.srce.hr/179590

Datum izdavanja:

8.4.2017.

Posjeta: 2.612 *