Stručni rad
https://doi.org/10.32762/zr.21.1.8
Compression Test of a Column Capital of Moise Palace in Cres
Željko Smolčić
orcid.org/0000-0001-7726-7721
; Sveučilište u Rijeci, Građevinski fakultet, Radmile Matejčić 3, 51000 Rijeka
Paulo Šćulac
; Sveučilište u Rijeci, Građevinski fakultet, Radmile Matejčić 3, 51000 Rijeka
Sažetak
The paper describes compression test of a column capital, about 500 years old, from the Moise palace in Cres. In the repair of the palace on the column capital, visible damage of unknown origin has been noticed. Due to the damage on the column capital, it was necessary to conduct the compression test to the prescribed service load. The aim of this paper is to demonstrate the need for cooperation between contractors, structural designers, conservators and use of laboratory testing for proof of bearing capacity and serviceability of structural elements. The results of compression test have shown that the column capital can withstand the expected service load.
Ključne riječi
column capital; damage; crack; compression; laboratory test
Hrčak ID:
217574