The statistical scatter of breakdown voltages of transformer oil - Part III

Vitaly Gurin
Marius Grisaru


Full text: english pdf 1.099 Kb

page 28-38

downloads: 320

cite


Abstract

The third part of the article about coefficients of variation (CV%) of breakdown voltage (BDV) of transformer oil discusses area effect and volume effect. Apparently, BDV decreases linearly with area on a logarithmic scale, but this does not apply to CV%. There is currently little data to make any quantitative recommendations. With an increase in the stressed oil volume by orders of magnitude, CV% decreases several times, but this estimate requires verification.

Keywords

area effect; breakdown voltage; coefficients of variation; electric strength; transformer oil; stressed oil volume