Abstract

The phase shifting transformers with on load tap changer are increasingly found in modern power supply systems, especially under the present conditions of the full opening of the electricity market. The construction of the Žerjavinec TS 400/220/110 kV for the first time introduces into the Croatian transmission system a 400/220/(10,5) kV 400 MVA phase shifting network transformer with on load tap changer. The present article highlights some specific aspects of phase shifting transformers in the light of their application in the Croatian system. For a more efficient use of the advantages of phase shifting transformers, the transformer of this type at Žerjavinec would need to be provided with a complementary transformer (pair), either within the Croatian transmission network or within the neighbouring systems.

Keywords

coordinated control; phase shifting transformer; transmission network