Skip to the main content

Original scientific paper

Synchronized phasor measurements in a dual layer hybrid state estimator

Vedran Kirincic ; University of Rijeka, Faculty of Engineering, Department of Electric Power Systems, Vukovarska 58, 51000 Rijeka, Croatia
Srdjan Skok ; University of Rijeka, Faculty of Engineering, Department of Electric Power Systems, Vukovarska 58, 51000 Rijeka, Croatia
Hrvoje Bulat ; Croatian transmission system operator company (HOPS d.o.o.), Kupska 4, 10000 Zagreb, Croatia


Full text: croatian pdf 852 Kb

page 1043-1050

downloads: 454

cite

Full text: english pdf 852 Kb

page 1043-1050

downloads: 665

cite


Abstract

The architecture of the proposed Dual Layer Hybrid State Estimator starts with the linear state estimator that only takes synchrophasors as inputs and calculates states of the buses with the deployed Phasor Measurement Units (PMUs) and their adjacent buses. These states are used to obtain the pseudo-measurements that are processed together with conventional SCADA measurements. As the relationship between the conventional measurements and the state variables is nonlinear, in this layer the iterative weighted least squares method is applied to estimate state of the complete power system. The developed formulation was tested on the IEEE systems as well as on the Croatian transmission power system model. The obtained results are compared with the classical solution that uses the conventional measurements and with another hybrid model. The hybrid state estimator based on the proposed architecture offers more accurate state estimation with enhanced filtering of measurements errors and with improved convergence capabilities.

Keywords

hybrid state estimator; Phasor Measurement Unit (PMU); power system state estimation; synchronized measurement technology

Hrčak ID:

112324

URI

https://hrcak.srce.hr/112324

Publication date:

20.12.2013.

Article data in other languages: croatian

Visits: 2.641 *