Skoči na glavni sadržaj

Izvorni znanstveni članak

https://doi.org/10.7305/automatika.2012.12.507

Electromagnetic Compatibility in Air Insulation Substation

Bochra Khelifi ; Prof. Nekhoul Bachir, Ph.D., Department of Electrical Engineering, Faculty of Science and Technology, University of Jijel - 18000 - Algeria
Bachir Nekhoul ; Prof. Nekhoul Bachir, Ph.D., Department of Electrical Engineering, Faculty of Science and Technology, University of Jijel - 18000 - Algeria
Kamal Kerroum ; Department of Electrical Engineering, Institut Pascal, Blaise Pascal University Avenue Carnot 34, FR-63037 Clermont-Ferrand, France
Khalil El Khamlichi Drissi ; Department of Electrical Engineering, Institut Pascal, Blaise Pascal University Avenue Carnot 34, FR-63037 Clermont-Ferrand, France
Dragan Poljak orcid id orcid.org/0000-0003-1205-4842 ; Department of Electronics, Faculty of Electrical Engineering, Mechanical Engineering and Naval Architecture, University of Split R. Boskovica bb, HR-21000 Split, Croatia


Puni tekst: engleski pdf 1.166 Kb

str. 416-424

preuzimanja: 831

citiraj


Sažetak

In this work, transient coupling between the bus bars of the Air Insulation Substation (AIS) and the control cable located at its proximity is analyzed. The present study accounts for the real complex geometry of the bus bars and the finite conductivity of the soil. A time domain formulation of the problem is proposed in this work. The direct time domain formulation based on the use of Transmission Line (TL) theory and the Finite Difference Time Domain (FDTD) solution method. The excitations are given in the form of the localized current or voltage generator, respectively, and related electrical field radiated by bus bars. To ensure the electromagnetic compatibility (EMC) requirements the current induced in the transmission cable is analyzed by means of the Pencil Method that will allow one to identify the dominant frequencies in the interference signal. Various illustrative examples are given in the paper.

Ključne riječi

electromagnetic coupling to transmission lines; FDTD method; substations; switching operation

Hrčak ID:

133192

URI

https://hrcak.srce.hr/133192

Datum izdavanja:

12.1.2015.

Podaci na drugim jezicima: hrvatski

Posjeta: 1.641 *