Skoči na glavni sadržaj

Pregledni rad

METHODOLOGY FOR DETERMINING THE ACTUAL PQ DIAGRAM OF A HYDROGWENERATORS

I. Ilić
Z. Maljković
I. Gašparac
M. Pavlica
D. Ilić-Zubović
V. Jarić
A. Višković
R. Belobrajić


Puni tekst: hrvatski pdf 4.698 Kb

str. 144-181

preuzimanja: 1.103

citiraj

Puni tekst: engleski pdf 4.698 Kb

str. 144-181

preuzimanja: 2.701

citiraj


Sažetak

This paper presents the methodology for determining the actual PQ diagram as a key document for any power generation unit. It describes all the limits of which a hydogenerator PQ diagram consists. There is detailed explanation of the theoretical basis of the procedures for their determination. It also contains a reference to the less researched problem of heating in the hydogenerator end region. The paper clearly shows and explains the sequence of the procedures which make up the methodology. Deatiled analysis and calculations, particularly using modern numerical programming tools, provide a good insight in generator performance and may serve as a preparation for testing and measuring. The measurement and testing data is processed and interpreted, and it is only on the basis of the result thus established that the limits for the permitted operation of the generator are positively determined. The final result of the testing conducted in accordance with the methodology proposed is actual PQ diagram: the real PQ diagram of the hydrogenerator, confirmed by the maesurement.

Ključne riječi

end region; heating; hydrogenerator; PQ diagram; syncronous generator

Hrčak ID:

13153

URI

https://hrcak.srce.hr/13153

Datum izdavanja:

27.2.2007.

Podaci na drugim jezicima: hrvatski

Posjeta: 6.361 *