Technical gazette, Vol. 24 No. 2, 2017.
Original scientific paper
https://doi.org/10.17559/TV-20151012082303
An improved method for high impedance fault detection in medium voltage networks
Sonja Ravlić
orcid.org/0000-0003-4825-5574
; Ravel Ltd., Brajkovićev priklaz 13, 10000 Zagreb, Croatia
Ante Marušić
; University of Zagreb, Faculty of Electrical Engineering and Computing, Unska 3, 10000 Zagreb, Croatia
Juraj Havelka
; University of Zagreb, Faculty of Electrical Engineering and Computing, Unska 3, 10000 Zagreb, Croatia
Abstract
This paper presents a set of rules for an intelligent algorithm of high impedance fault detection by observing the phase to ground voltage, phase to phase current and harmonics of fault current. Several techniques to detect high impedance faults already exist for example current injection in the neutral, superposing voltage signals, harmonic analysis, neural networks. The main disadvantage of all methods is that the normal system activity may cause false tripping of the protection device. Our goal is to give a set of rules for an algorithm that can make a secure decision that a particular feeder event is high impedance fault. The set of rules was carried out from simulation results simulated in MATLAB. The proposed approach was trained and tested with 200 data sets and provides excellent results.
Keywords
fault detection; Fourier transform; high impedance fault; medium voltage network
Hrčak ID:
179847
URI
Publication date:
14.4.2017.
Visits: 3.182 *