Skoči na glavni sadržaj

Izvorni znanstveni članak

Online refurbishment of old transformers

K. K. Murty
D. C. Jain
R. K. Agrawal
J. J. L. Kapil


Puni tekst: engleski pdf 1.070 Kb

str. 84-93

preuzimanja: 201

citiraj


Sažetak

This article focuses on refurbishment / reconditioning for extension of life-expectancy of old transformers of EHV (extra high voltage 66 kV class and above) class, which were continuously in service for more than 20 years in the State Transmission Utility of Madhya Pradesh in India.
The salient feature of this article for moisture refurbishment of old transformers was by adopting the criterion “% relative saturation of water in oil.” This selection criterion is different from the conventional practice in vogue of observing the deterioration trend of IR (Insulation Resistance) and PI (Polarization Index) values and the DGA (Dissolved Gas Analysis), etc. The reconditioning of all such old EHV transformers, precisely 205 units, was taken up “online” in a big way, avoiding long downtimes and frequent load shedding, etc., keeping in view dissatisfaction amongst the consumers at large. This project was completed over a period of five years.

Ključne riječi

moisture content, Karl Fischer titration, oil filter plant / machine, IR and PI

Hrčak ID:

275179

URI

https://hrcak.srce.hr/275179

Datum izdavanja:

6.4.2022.

Posjeta: 558 *