DGA monitor accuracy – Data and decisions

Tony McGrail


Puni tekst: engleski pdf 386 Kb

str. 34-38

preuzimanja: 67

citiraj


Sažetak

This article explores the intricacies of DGA monitor accuracy, emphasising the challenges in extracting dissolved gases from transformer oil. Despite international standards like IEC 60567 recommending a maximum accuracy of 15% for complete DGA systems, real-world application, as reflected in CIGRE brochures, suggests a potential deviation closer to 50%. The implications of varying accuracies on diagnoses, particularly when employing diagnostic tools like the Duval triangle, are analysed.

Ključne riječi

DGA; DGA monitor; accuracy; extraction method; CIGRE; diagnoses; Duval triangle