Skip to the main content

Original scientific paper

Estimation of Parameters for Synchronous Generator from Sudden Short-circuit Test Data Considering Rotor Speed Variation

Muharem Mehmedović
Zdravko Rabuzin
Tomislav Bičanić


Full text: english pdf 1.121 Kb

page 121-128

downloads: 1.711

cite


Abstract

Procedure to estimate parameters of synchronous hydro-generator (18 MVA) from sudden short-circuit measurement data is presented. Test performed was under small and slow speed variation and reduced excitation current. Data were collected in the form of sampled time series of measured armature voltage and currents
prior to and during the sudden short-circuit test. Neither the rotor speed nor the angle between rotor and stator were measured. Detailed method of initial and final estimation of parameters were also appraised (Prony's method and constrained minimization technique) considering behaviour of the rotor angle and speed
during the test.

Keywords

constrained minimization; estimation of parameters; Prony's method; sudden short-circuit test; synchronous generator

Hrčak ID:

18370

URI

https://hrcak.srce.hr/18370

Publication date:

15.11.2007.

Article data in other languages: croatian

Visits: 3.441 *