Skip to the main content

Original scientific paper

https://doi.org/10.17559/TV-20230327000482

The Time Response Analysis of a Hybrid Electronic Switch and Residual Current Devices System

Ahmet Yurtcu ; Occupational Health and Safety Program, Merzifon Vocational School, Amasya University, 05300, Amasya/Turkey
Mustafa Yagimli ; Department of Computer Engineering, Istanbul Gedik University, Yakacık, 34876, Istanbul/Turkey
Hakan Tozan ; College of Engineering and Technology, American University of the Middle East, Egaila 54200, Kuwait


Full text: english pdf 832 Kb

page 43-47

downloads: 325

cite


Abstract

Residual current devices are vital as they are used to protect humans from electric shocks and fire hazards. These devices detect the residual current in the grid, open the mechanism, and leave the grid without voltage. In this study, the time response of a newly designed hybrid system consisting of an electronic switch system and a residual current device to protect humans from hazards has been analyzed. A model consisting of capacitors and resistors has been used to simulate the human body. In the designed system, the average response time was found to be 1.37 ms, which operates with an average of 6.43 times faster than a conventional residual current device. The results of the study illustrated that the designed system leaves the circuit voltage-free much faster than a conventional residual current device and is more effective in protecting human life.

Keywords

circuit implementation; electronic switch; residual current device; time response analysis

Hrčak ID:

312881

URI

https://hrcak.srce.hr/312881

Publication date:

31.12.2023.

Visits: 746 *