Skip to the main content

Original scientific paper

THE NEUTRAL CONDUCTOR VOLTAGE IN A MEDIUM-VOLTAGE NETWORK DURING A GROUND FAULT

Matislav Majstrović ; Energetski institut Hrvoje Požar, Zagreb, Hrvatska
Hrvoje Olujić ; HEP Proizvodnja, Zagreb, Hrvatska


Full text: croatian pdf 1.000 Kb

page 328-349

downloads: 527

cite

Full text: english pdf 1.000 Kb

page 328-349

downloads: 5.625

cite


Abstract

Of all the ground faults that can occur in medium-voltage networks from the standpoint of human and equipment safety, the most problematic is a ground fault in a medium-voltage/low-voltage substation. The grounding system of a low-voltage network is directly connected to the grounding electrode of the substation. Therefore, each increase in the potential of the grounding electrode of the substation is transmitted directly via the neutral conductor into the customer's installation. For these reasons, in this article a detailed investigation is presented of the problem of determining the neutral conductor voltage in a low-voltage network during a ground fault at the medium-voltage level in a supply substation that is an element of a medium-voltage network with an isolated neutral point (star point). A computer model is presented for the analysis of the neutral conductor voltage in actual distribution networks. Two characteristic distribution networks located on karstic terrain are analyzed. The results obtained are compared to the results of measurements.

Keywords

distribution network; ground fault; low-voltage; medium-voltage; neutral conductor voltage; potential

Hrčak ID:

28985

URI

https://hrcak.srce.hr/28985

Publication date:

30.6.2008.

Article data in other languages: croatian

Visits: 7.388 *