Skoči na glavni sadržaj

Izvorni znanstveni članak

Aligning the economic and technical end of transformer life using online condition monitoring

Dr Bhaba P. Das


Puni tekst: engleski pdf 1.312 Kb

str. 100-110

preuzimanja: 273

citiraj


Sažetak

This paper presents a case study for a 30 MVA, 132/22 kV transformer in service for 35 years, which showed significant furans but stable DGA and other parameters. Online Condition Monitoring justified effective utilization of the transformer, i.e., load optimization to align technical and economic End-Of-Life within a planned replacement window in the next 5 years, achieving a 40-year economic End-Of-Life. This shift from timebased to condition-based operation supported informed decision-making while minimizing risk and maximizing return on investment, as presented in the paper.

Ključne riječi

Technical End-of-Life; Economical End-of-Life; Condition Monitoring; Diagnostics; Asset Management

Hrčak ID:

337358

URI

https://hrcak.srce.hr/337358

Datum izdavanja:

6.10.2025.

Posjeta: 415 *