Structural integrity of diesel generator set subjected to dynamic loads

Ivo Senjanović ; University of Zagreb, Faculty of Mechanical Engineering and Naval Architecture, Ivana Lučića 5, 10 000 Zagreb, CROATIA
Nikola Vladimir ; University of Zagreb, Faculty of Mechanical Engineering and Naval Architecture, Ivana Lučića 5, 10 000 Zagreb, CROATIA
Damjan Čakmak ; University of Zagreb, Faculty of Mechanical Engineering and Naval Architecture, Ivana Lučića 5, 10 000 Zagreb, CROATIA


Puni tekst: engleski pdf 3.315 Kb

str. 1-26

preuzimanja: 842

citiraj


Sažetak

The integrity of the diesel generator set (genset) in the emergency power plant of a Nuclear Power Plant is considered. The genset consists of the diesel engine, the generator, and the common base frame on elastic spring-damper elements clamped to foundations. The genset is exposed to the seismic load, the short circuit impulse, and the synchronization failure load. The problem is solved via the finite element method (FEM). In the FE model, the diesel engine and the generator are represented with two lumped masses rigidly connected to the base frame with sets of massless bars. Strength criteria are specified according to the Russian Federal Codes and Standards in the Area of Atomic Energy Applications. The necessary number of spring-damper elements for preserving the integrity of the genset is determined.

Ključne riječi

nuclear power plant; diesel generator set; common base frame; elastic springs; seismic load; FEM

Hrčak ID:

247770

URI

https://hrcak.srce.hr/247770

Datum izdavanja:

14.12.2020.

Posjeta: 1.371 *