Skoči na glavni sadržaj

Izvorni znanstveni članak

Significance of CO2/CO ratio in dissolved gas analysis

Mladen Banović ; Transformers Magazine
P Ramachandran ; ABB
Navin Rego ; Kahramaa
Pavel Justiz ; ORGREZ


Puni tekst: engleski pdf 235 Kb

str. 30-34

preuzimanja: 16.341

citiraj


Sažetak

According to the literature, the ratio of carbon dioxide and carbon monoxide (CO2/CO) for a transformer with a healthy cellulose insulation system should be between 3 and 11. If results of the dissolved gas analysis (DGA) of oil from transformers in service give the ratio value of CO2/CO less than 3, it means that the cellulose insulation is degrading rapidly. What is the meaning of this ratio if it is high; say greater than 15 or 20?

Ključne riječi

carbon monoxide; carbon dioxide; ratio; dissolved gas analysis

Hrčak ID:

182921

URI

https://hrcak.srce.hr/182921

Datum izdavanja:

8.1.2015.

Posjeta: 17.028 *