Skoči na glavni sadržaj

Izvorni znanstveni članak

RESEARCH OF TRANSFORMER MAIN INSULATION DESIGN RULES

Petar Gabrić ; Končar - Electrical Engineering Institute
Maja Glavinić ; Končar - Electrical Engineering Institute
Antun Mikulecky ; Končar - Electrical Engineering Institute
Vladimir Podobnik ; Končar Power Transformers, A joint venture of Siemens and Končar


Puni tekst: engleski pdf 2.198 Kb

preuzimanja: 326

citiraj


Sažetak

Kappeler research performed more than 50 years ago is widely used for HV transformers
insulation design. Even though the original experiment was done for oil ducts width from 0.5 to 6 mm, the
results have been extrapolated to ducts up to 100 and more mm without detailed publication that would
confirm the validity of this extrapolation.
This paper presents the experiment that aims to expand Kappeler research to oil duct width up to
30 mm. Model setup also allows creepage and barriers effect testing up to 30 mm.

Ključne riječi

power transformer; insulation; electric field; partial discharges; insulation design

Hrčak ID:

198824

URI

https://hrcak.srce.hr/198824

Datum izdavanja:

15.7.2017.

Posjeta: 901 *