Skoči na glavni sadržaj

Izvorni znanstveni članak

THE NEUTRAL CONDUCTOR VOLTAGE IN A MEDIUM-VOLTAGE NETWORK DURING A GROUND FAULT

Matislav Majstrović ; Energetski institut Hrvoje Požar, Zagreb, Hrvatska
Hrvoje Olujić ; HEP Proizvodnja, Zagreb, Hrvatska


Puni tekst: hrvatski pdf 1.000 Kb

str. 328-349

preuzimanja: 527

citiraj

Puni tekst: engleski pdf 1.000 Kb

str. 328-349

preuzimanja: 5.625

citiraj


Sažetak

Of all the ground faults that can occur in medium-voltage networks from the standpoint of human and equipment safety, the most problematic is a ground fault in a medium-voltage/low-voltage substation. The grounding system of a low-voltage network is directly connected to the grounding electrode of the substation. Therefore, each increase in the potential of the grounding electrode of the substation is transmitted directly via the neutral conductor into the customer's installation. For these reasons, in this article a detailed investigation is presented of the problem of determining the neutral conductor voltage in a low-voltage network during a ground fault at the medium-voltage level in a supply substation that is an element of a medium-voltage network with an isolated neutral point (star point). A computer model is presented for the analysis of the neutral conductor voltage in actual distribution networks. Two characteristic distribution networks located on karstic terrain are analyzed. The results obtained are compared to the results of measurements.

Ključne riječi

distribution network; ground fault; low-voltage; medium-voltage; neutral conductor voltage; potential

Hrčak ID:

28985

URI

https://hrcak.srce.hr/28985

Datum izdavanja:

30.6.2008.

Podaci na drugim jezicima: hrvatski

Posjeta: 7.388 *