Skip to the main content

Review article

APPLICATION OF PHASE SHIFTING TRANSFORMERS IN THE CROATIAN POWER SUPPLY SYSTEM

G. Jerbić


Full text: croatian pdf 1.100 Kb

page 216-231

downloads: 1.972

cite

Full text: english pdf 1.100 Kb

page 216-231

downloads: 801

cite


Abstract

The phase shifting transformers with on load tap changer are increasingly found in modern power supply systems, especially under the present conditions of the full opening of the electricity market. The construction of the Žerjavinec TS 400/220/110 kV for the first time introduces into the Croatian transmission system a 400/220/(10,5) kV 400 MVA phase shifting network transformer with on load tap changer. The present article highlights some specific aspects of phase shifting transformers in the light of their application in the Croatian system. For a more efficient use of the advantages of phase shifting transformers, the transformer of this type at Žerjavinec would need to be provided with a complementary transformer (pair), either within the Croatian transmission network or within the neighbouring systems.

Keywords

coordinated control; phase shifting transformer; transmission network

Hrčak ID:

13155

URI

https://hrcak.srce.hr/13155

Publication date:

27.2.2007.

Article data in other languages: croatian

Visits: 4.822 *