Transients Caused by Sequential Circuit Breaker Tripping Issued by Busbar Protection

Ivo Uglešić ; 1University of Zagreb, Faculty of Electrical Engineering and Computing, Unska 3 10000 Zagreb, Croatia
Igor Ivanković ; HEP-Transmission System Operator, Kupska 4 10000 Zagreb, Croatia
Viktor Milardić ; 1University of Zagreb, Faculty of Electrical Engineering and Computing, Unska 3 10000 Zagreb, Croatia


Full text: english pdf 415 Kb

downloads: 257

cite


Abstract

A study of transients in a high voltage substation 400/110 kV is presented in the paper. An analysis
was carried out after a fault on the 110 kV busbar, which caused severe damage in the substation.
Investigation was focused on a time frame of several sequential circuit breaker trippings. A first step
of the study was collection of data from the primary and secondary system in the substation and the
control centre. After numerous analyses of data an attempt was made to construct a precision model,
which could be used in the computation. Appropriate models were developed for circuit breakers,
voltage (potential) and current metering transformers, power transformers, surge arresters, overhead
lines and an equivalent grid. The components of the power system can be modelled for the very
particular purpose, which means that a different frequency model should be used and each element in
this analysis has a specific frequency response. An attempt was made at very detailed modelling of a
power transformer, air blast and SF6 circuit breakers. Computed results of fault currents were
compared with measurements captured by the disturbance recorders in the field, mainly in differential
numerical relays. Different switching schemes and different tripping sequences of several 110 kV
circuit breakers were analysed with a constructed model in the millisecond range. Models of circuit
breaker with different types of media, air blast and SF6 gas were used in the cases investigated.
Modelling of the circuit breakers’ electrical arc was an important item in all cases in order to take into
account the interaction between electrical arc and circuit current during the process of current
interruption. The Schwarz/Avdonin equation is applied to model the dynamic behaviour of an electric
arc. The fault studied was accompanied by a large short circuit current. For this particular case two
types of circuit breaker, air blast and SF 6 were modelled. An important conclusion from those
analyses was that sequential tripping of several circuit breakers does not cause superposition of
overvoltages, because interruption the current happens when it is passing through the zero. Even the
record from the substation and the disturbances recorder proves that each particular circuit breaker was
successfully opened. On that basis, focus was put only on the final opening of the breaker and its arc
extinction. The conclusion can be drawn that such a substation fault should have no influence on
excessive overvoltages that can threaten the insulation of components in the substation.

Keywords

Switching - Overvoltage - Circuit Breaker Model - Disturbance Recorder - Arc - Extinction - Computation