Transformers Magazine, Vol. 4 No. 5, 2017.
Original scientific paper
Condenser bushings condition monitoring
K.K. Murty
Abstract
This article focuses on condenser bushings monitoring, of both oil-impregnated and resin-impregnated paper bushings, for extra high-voltage class transformers in order to avoid a catastrophic transformer failure that might result from a failed bushing. A brief description of the online monitoring system is presented, highlighting its superiority over conventional offline monitoring practices. This is followed by a true case study and a specimen cost-benefit analysis related to a failure of a 160 MVA, 220/132/33 kV transformer and its assumed down time of 72 hours at a substation in India, caused by a failure of a 245 kV oil-impregnated paper bushing.
Keywords
bushing; tan δ; capacitance; infrared thermography