Skoči na glavni sadržaj

Izvorni znanstveni članak

The statistical scatter of breakdown voltages of transformer oil - Part IV

Vitaly Gurin
Marius Grisaru


Puni tekst: engleski pdf 933 Kb

str. 52-62

preuzimanja: 699

citiraj


Sažetak

The fourth part of the article reviews and summarises relevant studies on the critical relationship between the breakdown voltage (BDV) and temperature, providing insights and recommendations for further research. Different types of contaminants in different types of insulating liquids under certain conditions increase BDV with increasing temperature (positive dependence), whereas in others, it may reduce BDV (negative dependence). Additionally, the duration of exposure at specific temperatures and the direction of temperature change can significantly affect the instantaneous BDV value. The limited (only four sources) and sometimes conflicting data on the variation coefficient (CV%) underline the need for further systematic investigation, especially for new and alternative insulating liquids.

Ključne riječi

breakdown voltage; coefficients of variation; contaminants; effect of temperature; electric strength; oil; transformer