Skoči na glavni sadržaj

Izvorni znanstveni članak

On the energizing of a natural ester-filled transformer: Cold start for offshore application

Ahmed Gamil


Puni tekst: engleski pdf 1.637 Kb

str. 114-122

preuzimanja: 331

citiraj


Sažetak

In cold climates offshore applications, using natural ester liquids reveals challenges due to their higher pour points compared to mineral oil. Laboratory experiments have shown that the critical concern for transformers in cold climates applications is the temperature at which solidification begins, which is higher than the pour point. This study tested a natural rapeseed-based ester liquid for energizing at subzero ambient temperatures. A case study involved exposing a natural ester-filled transformer to -15°C for approximately 400 hours, followed by energization. Liquid samples were taken before and after energization to observe changes in properties under these conditions.

Ključne riječi

power transformer; cold climate; natural ester; partial discharge; thermal time constant

Hrčak ID:

333376

URI

https://hrcak.srce.hr/333376

Datum izdavanja:

7.7.2025.

Posjeta: 553 *