Skoči na glavni sadržaj

Izvorni znanstveni članak

https://doi.org/10.21278/TOF.SI1005721

Exergy Analysis of an Air Conditioning Process

Matej Đuranović ; Brod-plin d.o.o, Slavonski Brod, Croatia
Martina Rauch ; University of Zagreb, Faculty of Mechanical Engineering and Naval Architecture, Zagreb, Croatia
Antun Galović ; University of Zagreb, Faculty of Mechanical Engineering and Naval Architecture, Zagreb, Croatia
Marija Živić ; Mechanical engineering faculty, Slavonski Brod, Croatia


Puni tekst: engleski pdf 1.581 Kb

str. 1-12

preuzimanja: 515

citiraj


Sažetak

The exergy analysis of an air conditioning process in wintertime is presented in this paper. This process consists of mixing outdoor air with conditioned air, heating, humidifying, and reheating the air mixture. The air is heated in the heat exchangers by warm water at a temperature of 80/60 °C and humidified by spraying water at a temperature of 12 °C. The ratio of the mass flow rates of outdoor and conditioned air is varied, and it is upon this variable that the exergy analysis is performed. The five cases are analyzed with different outdoor air temperature values. It is shown that the heat transfer rate in the heat exchangers is the smallest at the ratio of mass flow rates of outdoor and conditioned air g1 = 0.45. The greatest exergy destruction is apparent in the heat exchangers, and the maximum exergy efficiency of the whole process ɛex = 0.71 is achieved at the ratio g1 = 0.45. According to the exergy criterion, this air conditioning is a relatively efficient process.

Ključne riječi

air conditioning; exergy destruction; exergy efficiency

Hrčak ID:

252565

URI

https://hrcak.srce.hr/252565

Datum izdavanja:

21.4.2021.

Posjeta: 1.051 *