Skip to the main content

Original scientific paper

https://doi.org/10.30765/er.38.3.9

Optimizing air velocity for the underfloor forced ventilation to protect a refrigerated warehouse from frost heaving

Jingfu Jia ; Ocean College of Hebei Agricultural University, Qinhuangdao, Hebei, China
Manjin Hao ; School of Architecture & Mechanics, Yanshan University, Qinhuangdao, Hebei, China
Jianhua Zhao ; Ocean College of Hebei Agricultural University, Qinhuangdao, Hebei, China


Full text: english PDF 840 Kb

page 321-327

downloads: 857

cite


Abstract

Forced or natural ventilation is the most common measure of frost heave protection for refrigerated warehouse floor. To optimize air velocity for the underfloor forced ventilation system of refrigerated warehouse, a steady state three-dimensional mathematical model of heat transfer is set up in this paper. The temperature fields of this system are simulated and calculated by CFD software PHOENICS under different air velocity, 1.5 m/s, 2.5 m/s or 3.5 m/s. The results show that the optimized air velocity is 1.5 m/s when the tube spacing is 1.5 m.

Keywords

refrigerated warehouse floor; forced ventilation; frost heave protection; steady three-dimensional; heat transfer; heat transfer performance; air velocity

Hrčak ID:

201153

URI

https://hrcak.srce.hr/201153

Publication date:

11.6.2018.

Visits: 1.432 *